HIGH-CAPACITY ET SERIES BATTERY PLATFORM

ET-51.2V200Ah-HV High-Voltage Battery System

MODEL · ET-51.2V200Ah-HV

ET-51.2V200Ah-HV doubles the ET module capacity to 200Ah and 10.24kWh while retaining a 51.2V module voltage. Four to ten modules form 204.8-512V systems with 40.9-102.4kWh nominal energy. The catalog lists 80A recommended and 100A maximum charge/discharge current, CAN/RS485 communication, natural cooling and IP21 protection for indoor stack or frame installations.

10.24kWhModule energy
51.2V / 200AhModule rating
4-10Series modules
40.9-102.4kWhSystem energy
80ARecommended current
100AMaximum current

For EPC contractors and integrators that need more energy per series position and a higher current path than the ET 100Ah system.

Technical values are based on the supplied LeforESS catalog and remain subject to the selected model datasheet.

204.8-512VNominal system voltage
185.6-576VOperating range
CAN / RS485Communication
IP21Indoor enclosure
Natural coolingCooling
90%Recommended DoD

Higher Energy per Module

A 40.9-102.4kWh ET Platform for Larger Loads

The 200Ah version is not merely a longer-runtime substitute. Its 100A maximum current and heavier 10.24kWh modules change cable sizing, handling, frame loading and PCS requirements.

01

Small commercial peak management

Build a high-voltage battery bank around verified demand peaks, tariff windows and inverter dispatch controls.

02

Workshop and facility backup

Use measured critical-load power and autonomy targets to determine whether the required configuration stays inside the four-to-ten-module range.

03

OEM system integration

Integrators can package the battery with their selected PCS and protection equipment after protocol and voltage approval.

Verified Product Data

ET-51.2V200Ah-HV Electrical and Mechanical Data

These catalog values define the 200Ah ET module and its approved series range. They must not be substituted with specifications from a low-voltage 51.2V 200Ah wall battery.

ModuleCell chemistryLiFePO4
Module energy10.24kWh
Nominal voltage51.2V
Capacity200Ah
Module dimensions (W x D x H)383 x 605 x 240mm
Approximate module weight77kg
SystemModules in series4-10 optional
Nominal voltage204.8-512V
Operating voltage185.6-576V
Nominal energy40.9-102.4kWh
Usable energy listed36.86-92.16kWh
Charge/discharge currentRecommended 80A; maximum 100A
EnvironmentWorking temperature0-60C
CoolingNatural cooling
Humidity5%-85% RH
Altitude<=2000m
Enclosure ratingIP21
IntegrationCommunicationCAN, RS485
InstallationStack mounting or iron-frame mounting
System dimensions (W x D x H)355 x 567 x 830-1850mm listed
Approximate system weight323-785kg
Storage temperature0-35C
ReliabilityRecommended depth of discharge90%
Cycle life listed>=6000 cycles
Warranty listed5 years
Certification listedCE, MSDS, UN38.3

Product specifications and configuration options must be confirmed against the selected model datasheet before ordering. The catalog lists system dimensions identical to the 100Ah platform despite the larger 200Ah module dimensions. Obtain a configuration drawing before publishing the assembled dimensions.

LeforESS ET-family high-voltage control unit and modules

Current and Mechanical Planning

A Heavier Module Changes the Installation Scope

At approximately 77kg per module, the 200Ah platform requires planned handling, rack support and service access. The battery quotation should therefore include the physical configuration, not only a module count.

80A recommendedNormal operating strategy should be checked against the recommended current, not designed only around the 100A maximum.
Frame engineeringConfirm the selected module count, support frame, anchoring and floor capacity for the quoted system weight.
Natural coolingMaintain the clearances and room conditions required to prevent heat accumulation around the installed modules.
Commissioning dataProvide inverter model, firmware and protocol requirements before configuring the BMS and control unit.

Technical Buying Questions

ET 200Ah Procurement Questions

What is the difference from the ET 100Ah system?

The 200Ah module stores 10.24kWh instead of 5.12kWh and supports 80A recommended, 100A maximum current. Its module weight and dimensions are also higher.

Can the bank be installed without an iron frame?

The catalog lists stack or iron-frame mounting. The approved arrangement depends on module count, local structural requirements and the supplied installation hardware.

Does 102.4kWh guarantee a specific backup time?

No. Runtime depends on usable energy, load profile, inverter efficiency, reserve SOC and operating conditions.

Is this the same as a low-voltage 51.2V 200Ah battery?

No. Individual modules are 51.2V, but the catalog system connects four to ten modules in series to create a high-voltage bank.